Chapter 7 - Electrical Wiring
ROUTING 24 VDC WIRING:
Following Airxcel’s low voltage wiring specications and local National Electrical Codes (NEC), route
the Roof Top Unit 24VDC supply wiring from its power source to the wire box. Use the chart below as a
guide knowing the amp draw listed on the unit rating plate to size the minimum wire size for use for the
distance in feet between the unit and your power supply.
This is a ve percent table which means at these amperage ratings at the listed distances, 5% of the power
would be lost to resistance.
24 VOLT DC CHART
Amps in Wire Watts at 24V #14 #12 #10 #8 #6 #4 #2 1/0 2/0 3/0
1 24 169 262 412 675
2 48 84 131 207 337 532
4 96 37 66 103 169 267
6 144 28 45 66 112 178 282
8 192 21 32 54 84 133 216
10
240 17 26 43 67 107 169 270
15 360 11 17 26 45 71 112 180 289
20 480 13 21 37 54 84 135 217 270 343
25 600 17 26 43 67 108 172 217 274
30 720 13 22 36 56 90 144 180 228
40 960 17 26 43 67 108 135 171
50 1200 13 21 34 54 86 108 137
ELECTRIC CIRCUIT
DC POWER REQUIREMENT: 1243 Watts
OPERATING CURRENT: 13 - 40 Amps
MINIMUM CIRCUIT AMPACITY (DC AMPS): 50
Follow all local and NEC (National Electrical Code) for proper sizing of wire AWG based on
Overcurrent Protection Device selected and the length of the wiring run to the air conditioner.
DANGER - SHOCK HAZARD
MAKE SURE THAT ALL POWER SUPPLY TO THE UNIT IS DISCONNECTED BEFORE
PERFORMING ANY WORK ON THE UNIT TO AVOID THE POSSIBILITY OF SHOCK
INJURY OR DAMAGE TO THE EQUIPMENT.